(1. School of Electronic Science and Engineering,Chongqing University of Posts and Telecommunications,Chongqing 400065,CHN;2. Chongqing Institute of University of Chinese Academy of Sciences,Chongqing 400714,CHN; 3. Chongqing Institute of Green and Intelligent Technology,Chinese Academy of Sciences,Chongqing 400714,CHN)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    文章提出一种基于 FPGA的红外光电导探测器温度控制系统,旨在解决小尺寸 PbSe器件因表面态占比大、边缘效应突出而导致的光电流波动问题。系统采用半导体热电制冷器

    Abstract:

    This paper presents a temperature control system for infrared photoconductive detectors based on a field-programmable gate array(FPGA),designed to address photocurrent fluctuations caused by the high proportion of surface states and prominent edge effects in small-sized PbSe devices. The system uses a semiconductor thermoelectric cooler(TEC)as the core actuator and combines a negative temperature coefficient thermistor with an analog-to-digital converter to achieve real-time temperature acquisition and feedback,implementing self-tuning fuzzy proportional-integral-differential(PID)control through the FPGA platform. Using the PID control algorithm,the system achieves precise control of the ambient temperature of the infrared detector by modulating the duty cycle signal and dynamically adjusting the current polarity and power of the TEC. Experimental results show that when the set temperature is 268 K( . 5℃),the fuzzy PID algorithm achieves temperature stability within ± 0. 2 K 91 s faster than the conventional PID algorithm. Further tests show that when the operating temperature drops from 300 K to 260 K,the Iph/Idark ratio of the detector increases by approximately 10%,and the noise decreases by 98. 4%,significantly improving detector performance. Comparative tests demonstrate that the temperature range of the TEC system is consistent with that of the liquid nitrogen-cooled low-temperature probe station, with a performance deviation of less than 5% at the same temperature. Through integrated design and intelligent control strategies,this system provides an efficient solution for temperature stability and performance optimization of small-sized infrared detectors and has broad application prospects.

    参考文献
    相似文献
    引证文献
引用本文

高旭,陈柯润,杨冬,申玟,申钧.基于热电制冷的小尺寸 PbSe光电导探测器温度控制系统[J].半导体光电,2025,46(6):1025-1033. GAO Xu, CHEN Kerun, YANG Dong, SHEN Wen, SHEN Jun. Temperature Control System for Miniature PbSe Photoconductive Detectors Based on a Thermoelectric Cooler[J].,2025,46(6):1025-1033.