Abstract:To improve the accuracy and engineering applicability of the double slope-assisted method in Brillouin scattering-based fast temperature/strain measurement for transformer windings, the influence of key factors on its error is systematically investigated. Considering the fluctuation of Brillouin frequency shift along the optical fiber in the practical measurement, Brillouin spectra with different signal-to-noise ratios, linewidths, and Brillouin frequency shift distributions are numerically generated based on the Gaussian model. The influences of the frequency of working point, linewidth, and the degree of Brillouin frequency shift deviation on the algorithm accuracy are investigated. Furthermore, a sensing optical fiber is installed on the transformer windings, and the above influences are investigated based on the measured Brillouin spectra. The results reveal that the frequency of working point, the degree of Brillouin frequency shift deviation, and the linewidth all have significant impacts on the algorithm accuracy. From the perspective of average value of/single space point"s Brillouin frequency shift error amplitude, the optimal working point’s frequency are the mean value of the Brillouin frequency shift on the optical fiber/the single points’ Brillouin frequency shift minus and plus half of the linewidth, respectively. The mean value of the Brillouin frequency shift error amplitude increases exponentially with the deviation coefficient of the Brillouin frequency shift. It is not recommended that the deviation coefficient of the Brillouin frequency shift exceed 0.3 to 0.4. The mean value of the Brillouin frequency shift error amplitude increases proportionally with linewidth. The critical signal-to-noise ratio corresponding to the mean temperature error amplitude of 3℃ is calculated for the linewidth ranging from 30 MHz to 200 MHz and the Brillouin frequency shift deviation coefficient ranging from 0 to 0.4. The reliability of the critical signal-to-noise ratio is validated using Brillouin spectra with different linewidths and deviation coefficients of Brillouin frequency shift. This work provides a theoretical support and technique reference for the real-time and accurate distributed temperature/strain measurement of transformer windings.